Attached Balcony Overhang
40 psf live + 10 psf dead + wind uplift
A second-floor balcony is the classic cantilever: joists reach 4–6 ft past the bearing wall with nothing under the tip. Strength is almost never the problem — on a measured 5 ft overhang of 2×10 SPF at 16″ o.c., the tip-bend check uses under 10% of capacity while the deflection budget consumes the whole ¼-rule allowance.
- Run the ¼ rule first: a 16 ft back span allows 4 ft of overhang, never more on timber joists
- Waterproofing at the wall penetration matters more than the wood: flashing failure rots the exact section carrying the negative moment
- Guardrail posts at the tip impose a 200 lb top-rail load — block the last 2 bays solid so the rail pulls on several joists at once
Bolting the balcony rim straight into brick veneer or stucco — the overhang has no real back-span connection and works as a lever on weak masonry
Forgetting wind uplift: balcony joists can be lifted, not just pressed, and that reverses the hanger load direction